The design system of automatic power reserve launch AVR for the training center.

We completed the design of the assembly, installation and adjustment of ATS for the building of the training center.

Details below ..

 

DESIGN AUTOMAIC POWER RESERVE START

Download the draft scheme AVR avtokad dwg please follow the link

Situation 1. Work in the regular mode.

· Available high-quality food from the main input (Parallel two inputs). Its presence is signaled by a phase control relay.

· Consumption of the entire system does not exceed the set value.

Ø Generator off.


Ø Power supply from the main input

PROJECT DOCUMENTATION

Situation 2. The power from the main inputs disappears or the food is of poor quality.

· Low or very high voltage on one or several phases. Indicator - phase control relay.

Ø Generator at work

Ø The system power is fully transferred to the generator.

Situation 3. Excess consumption by the system.

· The total power consumption of both outputs from the ATS by one of the phases exceeds the set value (9 KVA) for a specified time (20 seconds).

Ø Generator at work

Ø 5 seconds after starting the generator Output 1 power supply - from the generator

Ø Output 2 power supply - from the main input.