Design of automatic fire alarm system for Medical Center

Our design company completed the installation, design and commissioning of the automatic fire alarm system in the building of the Medical Center.

More details below …

 

 

DESIGNING APS

Purpose of the SAPS project

Address-analog fire alarm system (ASPS) is designed for:

· Detecting the occurrence of a fire and (or) smoke site at an early stage of fire development;

· Transfer of the message on the above situations to the fire alarm panel;

· Launch of the fire alarm system;

· Start the smoke removal system in the smoke area;

· Shutdown of general ventilation in case of fire and control of equipment of engineering systems of a building.

1. Characteristics of the facility equipped saps

The protected object consists of two adjacent buildings with an underground structure and a basement and an adjoining conference hall.

In the basement and underground structures are located:

medical, office, technical, commercial premises, as well as warehouses and production facilities, cooking workshops;

On the ground floor there are:

registry, reference, doctors' offices, commercial premises, office and technical premises, premises for cooking;

On the second floor are located:

doctor's offices, procedural, operating rooms, radiation diagnosis rooms, service and technical premises;

On the third floor are located:

hospital wards, doctors' offices, service and technical premises;

On the fourth floor are located:

hospital wards, operating rooms, laboratories, doctors' offices, service and technical premises;

On the fifth floor there are:

hospital wards, doctors' offices, service, technical and administrative premises;

On the sixth floor are located:

hospital wards, doctors' offices, service and technical premises;

On the seventh floor are located:

 operating units and doctors' offices;

The eighth floor is technical.

2  Basic technical solutions PS

3.1 Applied equipment in fire alarm design

The project uses an analogue address and fire alarm panel XLS 80 e manufactured by HONEYWEL .

The system includes:

· The address receiving control fire device (ATCM) XLS 80 e with power supply and two built-in loops - 2 pcs.

· Stub extenders for two stubs -5 pcs.

· RS- 232 interface module with galvanic isolation - 2 pcs.

· Adam 4571 L single-port data gateway - 2 pcs.

· Network module NGM - 2 pcs.

· Relay module TC810E1040 - 6 pcs;

· Analogue analogue smoke detector TC 806 E 1012 M 01 - 875 pcs.

· Thermal fire detector TC 808 E 1051 V 01 - 10 pcs

· Mounting base 14506414-07 - 825 pcs.

· Mounting base with insulator KZ 14506414-06 - 60 pcs.

· Manual analogue addressable detector MCP 5 A - 70 pcs.

· Fire alarm light sounder EMA24 FRSS - 3pcs

· Power supply Skat 1200I7 - 1 pc.

· EBI server with software. - 1 set

· ARM guard posts - 2 sets

3.2 Principle of construction of the MTA

In accordance with the “Technical requirements for the design of fire protection of the medical rehabilitation center,” the project provides for the protection of all the premises with an analogue analog fire alarm system (ASPS) regardless of the area, except for the premises:

· With wet processes (showers, bathrooms, sinks, etc.);

· Ventilation chambers (inflow, as well as exhaust, not serving industrial premises of category A or B), pump water supply, boiler rooms, etc. for engineering equipment of the building, in which there are no combustible materials;

· Categories B4 and D on fire danger;

· Stairwells.

In accordance with paragraph 13.2.2 of SP 5.13130.2009, the maximum number and area of premises protected by a single ring or radial loop with addressable fire detectors is determined by the technical capabilities of the receiving and control equipment, the technical characteristics of the detectors included in the loop and does not depend on the location of the premises in building.

In accordance with clause II 11.2 of the NPB 110-03, the space behind the suspended ceiling in the corridors is protected by automatic smoke fire detectors in the presence of cables and NG-type wires with a total volume of combustible mass from 1.5 to 7 liters per 1 meter of cable line.

The analogue optical-electronic smoke detectors TC 806 E 1012 M 01, which react to particles of solid or liquid products of combustion and pyrolysis in the atmosphere, installed on the main ceiling, on a suspended ceiling and behind a suspended ceiling, are used as means of detecting fire in protected areas .

In the premises of the cooking shops on the 1st floor, installation of thermal analogue detectors TC 808 E 1051 V01 with a maximum response temperature of 780 is provided .

On escape routes and staircases, installation of MCP 5 A manual address detectors at a height of 1.5 m from the floor level is provided for on the wall .

The interrelation of ASPS with other systems, technological and electrical equipment of the building is provided by the formation of the following commands:

· To start smoke removal in case of smoke in the smoke removal area;

· To launch a warning system and evacuation management in case of fire;

· To disable general ventilation;

· Stopping and lowering elevators to the main landing floor.

· To unlock the doors to the access control system.

2.1. Characteristics of the equipment

2.1.1. The address receiving control fire appliance (ATCM) XLS 80 e includes a case with a display and a keyboard, a power source and a central processor board, two built-in fire alarm loops. Additionally completed:

· Stub extenders for two stubs - up to 3 pieces per device.

· RS- 232 interface module with galvanic isolation - 1 pc.

· Network module NGM - 1 pc.

The algorithm works XLS80e fully programmed. The case contains two 12V / 12 Ah rechargeable batteries. Control commands are entered from the built-in keyboard, the LCD display shows the system status, including descriptions of the monitored zones, outputs and modules. Data can also be entered from the keyboard of a personal computer (PC). Network module NGM  allows you to organize work on the Arc Net network with other panels.

· The processor of the “master” panel synchronizes clocks and calendars of the “slave” panels.

· Event memory becomes common memory for events of all panels with sorting in chronological order.

· Fire detection zones and exits (starters, sounders) receive a unique sequence number in the system as a whole and are displayed as elements of one large system. Also, each panel has its own unique sequence number in the system.

· Information from each panel on the Arc Net network is displayed on any other panel instantly without delay.

· Any panel can display system-wide events or just selected panels. Any panel can send its own alarms to any other selected panels.

· The interface to connect panels to the network Arc Net is intelligent and high-speed. It uses a modified RS485 protocol with a sync generator on both sides of each node. This means that any malfunction or loss of communication on any part of the Arc Net network does not affect other parts. In addition, the Arc Net network has a ring topology and in case of loss of communication anywhere, the system will automatically find an alternative route for delivering information from the other side of the ring.

· In the event of a fault in the Arc Net bus, the panels continue to perform their functions by switching to offline mode.

· Control passwords in the system are synchronized across the “master” panel.

· The command to turn off the buzzer, given by the user of one panel, is executed by all panels of the system. The command to turn off the sirens also works.

· The use of “sectors” allows for high reliability of fire detection and minimizing the likelihood of false alarms during various activities at the facility.

2.1.2. Automated workplace.

 Includes an EBI server with software that allows you to implement control, programming and visualization of the system. The network solution of the organization of the automated workplace allows you to organize remote automatic workstations

2.2. Elements of the address analog loop

2.2.1. Address and analog smoke detector TC 806 E 1012 M 01

The detector is designed to detect a fire in the premises when smoke appears. The detector is constantly monitored for contamination, using algorithms that minimize the number of false alarms, including sensitivity compensation. It has easy access to a sensitive chamber for cleaning. The detector has:

· Decade address switch.

· Optical dispersion camera.

· Operating temperature range -30C to + 60C.

· Led indicator.

· Ability to connect an external indicator.

· Mounted on a base.

2.2.2. Manual address fire detector MCP 5 A

A manual addressable fire detector is used to give an alarm manually, by breaking safety glass. The detector has:

· Decade address switch.

· Alarming with glass breaking.

· The degree of protection of the housing IP-44 .

· LED indication of performance.

· Testing with a special key.

· Operating temperature range -30C to + 70C.

2.2.3. Thermal maximum-differential detector TC 808 E 1028М01

It is used in cases when the environmental conditions do not allow the use of smoke detectors. When the set level is exceeded or a certain temperature growth rate, the detector sends an alarm signal to the control panel. The detector has:

· Decade address switch.

· 5 working states of the sensor: alarm, low sensitivity, normal condition, high sensitivity, alarm.

· Differential and maximum fire detection criteria.

· Testing with magnet or software with control panel.

· Operating temperature range -30C to + 60C.

· Led indicator.

· Ability to connect an external indicator.

· Mounted on a base.

2.2.4. Relay module TC810E1040 .

It is used to control the engineering systems of the building in case of fire.

3. Calculation of battery capacity

The table shows the power-consuming devices included in the PPK.

No. p / p

Instrument Name

 

Count

PC

Current consumption in dej mode, mA

Current consumption in alarm mode, mA

Note

 

Current panel

one

0.165

0.215

 

 

Loops

eight

0.2

0.2

 

 

RS232 board

one

0.005

0.005

 

 

NGM Network Module

one

0.006

0.006

 

 

Total given the number

 

1.776

1.781

 

The capacity of the installed battery is 12 A / h. To ensure the normal operating time of the system, you must use an external battery. The capacity of the battery will be at least 43 A / h. on each panel.

4. General system installation instructions

Installation and commissioning should be carried out by a specialized organization with an appropriate license. Installation of hardware should be performed in accordance with the requirements of this project documentation and RD 78.145-93.

Deviations from the project documentation during installation are not allowed without the consent of the project organization - the project developer. It is not allowed to replace some technical equipment with others having similar technical and operational characteristics, without coordination with the project organization.

Before installation, check the cable conductors for open, communication, earth, and insulation resistance. Examine the technical documentation supplied with the equipment. Check cables for open circuit, connection, insulation resistance. When cutting cables for connecting to equipment, leave a reserve of lengths for a possible 10-fold connection, unless other dimensions are given.

Mark the cables at the ends of the tracks and at the branches. Cables and wires knit in bundles with clamps or thread through 1.5 meters. Cables laid in boxes, knit through 1 meter. When laying cables to withstand the internal bending radius of at least 2 diameters of the cable. Joint laying of loops and connecting lines of the fire alarm system with lines with voltage over 110 V is not allowed. When parallel laying open loops and connecting lines of fire alarm with lighting cables, the distance between them must be at least 0.5 m.

 Designs for protection of fire alarm wiring from mechanical damage are included in the section of the project "Cable route system" АКС.093.012. Install the equipment and connect the cables to the equipment according to the skeleton scheme, floor plans, blocking points, and also according to the technical documentation for the equipment being installed. When performing work, follow the requirements: SP 5.131130.2009,

SNiP 3.05.06-85; NPB 88-2001; Airbag 110-03; SNiP 21-01-97; SNiP 12-03-99; SNiP 12-04-02; PUE edition 6; BCH-59-88; BCH-60-89; BCH-600-81; RD 78-145-93 Ministry of Internal Affairs of Russia; RD 78-145-93 Parts 1.2 of the Ministry of Internal Affairs of Russia; RD 78.36.003-2002; Labor Protection Regulations RM-016-2001 RD 153-34.0-03.150-00; VNP-001-01; TT.78.36.003-99; "Instructions for the construction of the GTS"; SNiP 3-4-80; Airbag 54-96; Airbag 51-96.

4.1. System Installation Guidelines

The fire alarm detector cables should be made with a cable KPSVEVng Ls 2x0.75. The cable is designed for mounting loops of addressable fire alarm systems. According to the General Designer of fire hazardous areas in the building there. Loop resistance not more than 40 ohms. Joint laying of loops and connecting lines in one box, bundle, tray with lines with a voltage of 110 V and more is not allowed.

Attach detectors to suspended ceiling fixtures in rooms with overhead shelves. In rooms without suspended ceilings and behind suspended ceilings, the detectors should be fixed to the ceiling. When installing detectors, you must comply with the following requirements:

Install detectors no closer than 500mm from the lamps.

The maximum distance from the wall - no more than 4m. (it is allowed to increase to 4.5 m. if the installation height does not exceed 3.5 m.).

The distance between two adjacent detectors is not more than 9m.

Hand-held detectors should be fixed to the wall at a height of 1.5 m from the floor.

 Cable routing to perform:

- along the corridors on the trays;

- on rooms with suspended ceilings and in the attic on the cable.

- in the basement in the box;

- on rooms without suspended ceilings in the box.

The detectors installed behind the suspended ceiling are provided with a connection of LED indicators that allow visual observation of the status of the detectors. Indicators should be installed below the suspended ceiling with fastening to the ceiling or wall structures.

4.2. Power supply

Power supply system run on the 1st category of power supply.

For backup power, rechargeable batteries are provided that provide the standard operating time of the PS system.

For the power supply of the equipment of the Union of Right Forces, a group of the ShchOP shield is provided.

4.3. Safety requirements

Work with technical means is necessary to comply with the EMP.

Installation and commissioning should be started only after the implementation of safety measures in accordance with SNiP III -4-80.

When working with hand-held power tools, you must comply with the requirements of GOST 12.2.013-87.

When working with a building and assembly gun, it is necessary to observe the requirements of RTM 36.6-88 “Powder tools, types, technical data. Application area. Storage and repair. When working at heights it is necessary to use only ladders and ladders. The use of improvised means is strictly prohibited. When using ladders, the presence of a second person is required. The lower ends of the ladder should have stops in the form of metal spikes or rubber tips.

When installing, adjusting and maintaining technical equipment, it is necessary to be guided by the sections on safety of technical documentation of manufacturers, departmental instructions on safety when installing and adjusting control devices and automation tools.

1.1. Requirements for repair and maintenance

The maintenance of the installed equipment is carried out by the personnel of the “Customer” who has the appropriate training and qualification. The service intervals should be carried out in accordance with the technological description for each device.

Service interval:

- monthly THAT

- quarterly MOT

- annual maintenance

in accordance with the technical description of the equipment.

1.2. Fire fighting activities

Installed equipment meets fire safety requirements in accordance with GOST 12.2.007.0-75.

1.3. Environmental protection

During the implementation of this project and in the subsequent exploitation of gaseous, liquid and solid wastes no harmful substances are formed.

Additional measures to protect the environment are not required/