Hotel electrical Security Measures. Lightning Protection.

Hotel Lightning Protection drawings have been made.

проект заземления рабочая документация

Electrical Security Measures. Lightning Protection.

The design envisages an earthing system type TC-5 starting from MOB busbars.

Earthing of busbar PE In the main electrical room and in the main distribution board is provided with the help of the external circuit of the earthing device with resistance not greater than 4 Ohm. Busbars PE and N are interconnected in the main distribution board room.

All metal parts of electrical installations normally not under voltage, as well as all metal pipeworks, ductworks, cable trays, ducts, conduits for cable routing, all cabinets of distribution boards and control boards should be earthed.

The Multifunctional complex is subject to protection against lightning, with measures fulfiled for category 2 of norms CO 153-34-21.122-2003.

An overcurrent protective devices and residual current devices (PCD) shall be used for automatic disconnection of supply. Also, PCD shall be used for additional protection against direct contact in final distribution.

Calculation of Earth Termination Network

- Estimated resistivity of top layer of soil: p 1= 300 Ohm*m,

- Estimated resistivity of under layer of soil: p2- 60 Ohm *m,

- Estimated soil resistivity:

р 1- Estimated resistivity of top layer of soil Ohm ‘m, p2- Estimated resistivity of under layer of soil Ohm ‘m, S- Building area, m2; hi- Thickness of top layer of soil, m, a,13- extendable coefficients.

4. Resistivity of concrete foundation (Ohm)

к- Climatic factor;

р- Estimated soil resistivity (Ohm "m);

6. Resistivity of vertical ground:

- Estimated resistivity of horisonfal circuit.

Rn= Rl/kn- 16,9107

Rl-resistivity of horisonfal ground; kn-factor of usage of ground strip;

- Estimated resistivity of electrodes.

Rs- R2/(N‘k3) = 0,55164 ,

R2-resistivity of electrodes; кэ-factor of electrodes usage;

N-electrodes quantity;

Estimated resistivity of earthing circuit:

EARTHING NOTES

- THE EARTHING ТАРЕ AND ALL EXPOSED CONNECTIONS SHALL BE MADE OP 40x4 mm GALVANIZED STEEL TAPE (Ee/Zn). THE DOWNCONDUCTORS ON CONCRETE COLUMNS SHALL BE MADE 0Г 8 mm GALVANISED STEEL ROD.

- ALL CONNECTIONS IN GROUND AND IN CONCRETE SHALL BE WELDED AND CORROSION PROTECTED. ALL CONNECTIONS SHALL BE DONE OVERLAPPED WITH WELDED LENGTH 100mm.

- NEW EARTHING PROTECTION SYSTEM SHALL BE FULLY TESTED. EARTHING RESISTANCE SHALL BE LESS THAN 4 Ohm, OTHERWISE ADDITIONAL VERTICAL GROUNDING ELECTRODES SHALL BE INSTALLED.

- STEEL UTILITIES PIPES SHALL BE CONNECTED TO THE PROTECTIVE EARTHING.

- PROTECTIVE EARTHING PERIMETER CONDUCTOR 40x4mm TO BE INSTALLED AT 1000mm AFEL IN TRANSFORMER ROOM, IN 10kV SWITCHROOM, IN LV SWITCHROOM AND BE CONNECTED TO THE EATHING BUSBAR. ALL OPEN CONDUCTIVE PARTS OF ELECTRICAL EQUIPMENT SHALL BE CONNECTED TO THE PROTECTIVE EARTHING CONDUCTOR.

6. PROTECTIVE EARTHING PERIMETER CONDUCTOR AND MAIN EARTHING BAR IN TRANSFORMER ROOM, IN 10kV SWITCHROOM TO BE DESIGNED BY SUBCONTRACTORSPECENGELECTRO”

- MAIN EARTHING BARS IN 0,4kV SWITCHROOMS ARE BUILT. EARTHING BARS PAINTING SHOULD BE PERFORMED TO THE REQUIREMENTS.

 

Lightning protection

Lightning protection shall be arranged in accordance with the Instruction on the arrangement of lightning protection of buldings, structures and industrial service (50 153-34.21.122-2003). The buiding shall have category II lightning protection, because a lightning strike may cause damage to electrt and electronic equipment and failure of computers with data loss, which is inadmissible for offices.

A sheet-pie enclosure around the buiding perimeter is used for earthing and also for potential equalization inside the buiding. A llightning arrester 01 made of 8 mm2 diameter steel wire with mesh size of 10 x 10 m shall be placed on the roof of the building. Grll crossing points shall be welded. The Lightning protection mesh should be installed on the root cabling support, or could be installed over the roof stab if flashing and thermal insulation is uninflammable.

Lightning arresters made of 8 mm2 wre shall be laid to the earthing with spans not smaller than Б meters along the buiding perimeter. Place of current drainage wires shall be coordinated with the architects during development of the Working Documentation.

Connections of the lightning arrester grill with current drainage wires and of current drainage wres with earthing bars shall be welded.

Technical requirements for manufacturing of power supply boards, power distribution boards and motor control centres (MCC).

1.    Electrical boards shall be cabinet type, for wall mounting or floor installation, IP30, with lock-up door.

2.    Supposed cabinet dimensions: - 250mm deep, up to 850mm wide including side compartment for feeding and outgoing power and control cables. Cabinet dimensions shall make position for 10-15% of spare apparatus in it.

3.    External power and control cables sized up to 6sg.mm. shall be connected to special wire grips installed along the cable compartment.

4.    Cables should run in from top or bottom of the board.

5.    All apparatus installed within the board shall be of stationary type.

6.    Internal wiring shall be provided with copper busbars or flexible core copper wires. Not more than 2 wires shall be connected to a single wire grip.

7.    All clamps and grips shall be available for inspection and maintenance (tightening check) without other circuits and apparatus of being dismantled.

8.    Separate "N"and "PE" busbars with sufficient quantity of individual clamps for outgoing cables shall be provided. Clamp quantity shall comply with the board diagram.

9.    All apparatus, power and control cables shall be labeled according to the technical documentaton for the board. Board name plate shall be intailed at the upper part of the cabinet centered.

10.    Collecting busbars or wiring used intead shall have alphanumeric or colour labeling complying with PUE, paragraph 1.1.29 and 1.1.30. Colour labeling should be done with tape or bus painting.

Power wiring connected to phases L1, 12, L3 and to N and PE busbars shall have typical cover colours.

11.    Board manufacturer shall provide together with the unit the following technical documentation :

-    single line diagram (circuit and control schematic);

-    front view, including the view without the front door;

-    specification with a schedule of installed equipment, type, short descrition and manufacturer;

-    brief installation instructions for cable lead-in method and cable mounting method within the cabinet;

-    certification;

-    report.

12.    Main low voltage switchboard cabinets (ГРУ-0,4кВ) shall be floor installation type with double-sided maintenance access, incoming and sectional breakers to be withdrawable type, feeder breakers - stationary type; dimensions to be defined by supplier contractor.

13. All apparatus and manufactures used shall have certificates of conformance and be resistible to short circuit currents.

14. All deviations from the design solutions of singe line diagram shall be agreed with the design originator