Working documentation "Interior light"

Our company developed design working documentation "Interior light".

design lighting hotel

General instructions lighting

Working documentation "Interior light" facility located at: Moscow, MC is in accordance with the "Terms of Reference for the development of working documentation" technological tasks, architectural - construction plans and decisions agreed upon with the customer.
Working documents executed in accordance with the applicable rules and regulations.
In the working document, the following types of coverage:
- Work;
- Emergency (evacuation, back);
- Repair.
Group net operating and emergency lighting are performed for 380/220 V, 50 Hz.
Voltage repair network - 36 V.
The illumination of premises is accepted at rates reflecting the decisions taken in the approved project and customer requirements, technology requirements and the requirements of the interior.
Adopted by the following indicators light to the main premises:
- Dispatcher, server, motocross 400 lux;

- Office 300 lux;
- Premises security services 300 lux;
- Premises eating 200 lux;
- Switchboard 150 lux;
- Technical premises (ventilation chamber, pump), 150 lux;
- Lobbies, corridors, halls 150 lux;
- Storage areas 100 lux;
- Toilets, showers 75 lux;
- Premises of 300 lux;
- Stairwells 100 lux.
Emergency lighting is divided into evacuation and back.
Evacuation coverage is divided into: the lighting of escape routes, emergency lighting danger zones and evacuation lighting of large areas (anti-panic lighting).
Emergency lighting is provided in the event of power failure and task lighting is connected to a power source that is independent of the power supply working lights.
The system is powered by an emergency input distribution apparatus for fire protection systems and power systems to ensure safe evacuation in case of fire .
Lighting of escape routes in the premises should be provided along the routes of evacuation:
- In the corridors and passageways on the evacuation;
- Areas of change (delta) above the ground or surface;
- In the area of each change of direction the route;
- At the intersection of passageways and corridors;
- A flight of stairs, each step needs to be illuminated by direct light;
- Before leaving the emergency exits;
- Before every point of care;
- At the locations of emergency communication equipment and other tools designed to alert you to an emergency;
- At the locations of the primary means of fire;
- At the locations of the evacuation plan.
Lighting control complete
- For office premises, industrial premises, etc. - With the help of local switches installed at the entrance to the room at a height of 0.9 m, respectively, from the level of the finished floor;
- For walk-through of the building premises (staircases, corridors, lift lobbies, rooms vestibule groups, etc.) - a centralized automatic control room of the premises, subject to natural light, if necessary.

For some areas with design fixtures DALI control system is required. Specified by the dispatching system project .
Binding and the location of the equipment specify by Lighting Specification for Park of Elektra company.