Design of interior architecture

We have elaborated design of interior architecture for building.

design AR

GENERAL NOTES ARCHITECTURE FITOUT

2. BUILDING DATA

2.1 The building is classified by the following features:

  • Fire-resistance rate - I.
  • Structural fire hazard class - С0.
  • Building criticality rating - high.
  • Class of facility - КС-3.

Functional fire hazard class:

  • Ф2 (recreational, cultural and educational facilities)
  • Ф3 (buildings of public service firms)
  • Ф4 (Buildings of educational institutions, scientific and design organizations and government administration)
  • Ф5 (manufacturing plants or warehouses)

3. INTERIOR DESIGN SOLUTIONS

3.1 All materials used in the working project must possess all required certificates and permits: certificate of conformity, fire safety certificate and Sanitary and Epidemiological inspection report.

3.2 Accomodate all LEED GOLD requirement in Working documents

3.3 The project is developed in accordance with applicable building codes and sanitary regulations of Russian Federation, as well as Federal Law №384-FZ ("Technical Regulations on safety of buildings and facilities).

3.4 Doors

3.4.1 Before the production of doors and gates, the manufacturer is obliged to perform a control measurement of dimensions of the openings.

3.4.2 The manufacturer must provide and agree with the developer of the project the range of doors and gates corresponding to the designed specifications.

3.4.3 Doors on escape routes must be equipped with self-closing mechanism (door closer), pair of doors must be additional equipped with coordinating the closing sequence system of the half-doors and locks with "anti-panic".

3.4.4 The device for emergency opening of doors of evacuation exits ("anti-panic") with force when opening not more than 50N for doors emergency exits from each floor of the corridors, halls, foyers, lobbies and stairwells.

3.4.5 On the paths of movement of disabled persons doors equipped with door closers with delay closing at least 5 sec, with an effort at opening not more than 19.5Nm.

3.4.6 On the paths of movement of the disabled persons abutment piece does not exceed 0,014 m.

3.4.7 The manufacturer is obliged to coordinate structural components installation of gates and doors with the developers of the project.

3.4.8 The firm-manufacturer of doors and gates is determined by the Customer.

3.4.9 Locking devices and fittings gates and doors is determined by the Customer.

3.4.10 Design of the doors opening to the zone of construction and assembling works according to the design project (Inferior Finish) indeterminably the contractor. Considering fire security requirements and access for limited mobility people.

3.4.11 Dimensions and characteristics of external doors, examine the package

3.4.12 Doors of lift lobby with retractable sealmake, hinged with gaskets in rabbet ledges, devices of self-closing (door closer) and with steel plate

3.5.13 Door specification please see in addition with MEP design

PROJECT NOTES

1. THE RELATIVE REFERENCE MARK ±0.000 ACCEPTED LEVELS AFTER FINISHING THE FIRST FLOOR, WHICH IS EQUAL TO AN ALTITUDE OF 5,000 IN THE BALTIC SYSTEM.

2. GREYED OUT LINES IN PLAN BACKGROUND REPRESENTS ARCHITECTURAL AND CORE&SHELL ELEMENTS AT FLOOR.

GENERAL NOTES

1. ALL WORK SHALL COMPLY WITH APPLICABLE LOCAL AND MUNICIPAL BUILDING CODES, AS WELL AS ANY AND ALL REGULATORY AGENCIES. GENERAL NOTES SHALL APPLY TO ALL DRAWINGS.

2. THE TERMS "CONSTRUCTION CONTRACTOR," "GENERAL CONTRACTOR," AND "CONTRACTOR" SHALL BE UNDERSTOOD TO BE THE SAME UNLESS SPECIFICALLY NOTED OTHERWISE.

3. THE CONTRACTOR SHALL VERIFY ALL JOB CONDITIONS, DIMENSIONS AND DETAILS PRIOR TO CONSTRUCTION, AND AS ANTICIPATED OR INFERRED PRIOR TO PRICING OR BIDDING.

4. DESIGNER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR OMISSIONS WHICH WOULD INTERFERE WITH THE SATISFACTORY COMPLETION OF THE WORK, PRIOR TO THE START OF ANY AND ALL WORK.

5. ALL WORK, WHETHER SHOWN OR IMPLIED, UNLESS SPECIFICALLY QUESTIONED, SHALL BE CONSIDERED FULLY UNDERSTOOD IN ALL RESPECTS BY THE CONTRACTOR, AND HE/SHE WILL BE RESPONSIBLE FOR ANY MISINTERPRETATIONS OR CONSEQUENCES THEREOF FOR ALL WORK ON ALL DRAWINGS.

6. UPON COMPLETION OF THE JOB, THE CONTRACTOR SHALL SUBMIT CERTIFICATES OF INSPECTION AND A CERTIFICATE OF SUBSTANTIAL COMPLETION.

7. CONTRACTOR SHALL DEVELOP AND IMPLEMENT LEED GOLD LEVEL CREDIT. SPECIFIC SUBMITTALS ARE REQUIRED TO ACHIEVE THE LEED REQUIREMENTS.

8. ALL THE NECESSARY MATERIAL CERTIFICATION SHALL BE SUBMITTED.

9. DRAWINGS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE.

10. DRAWINGS ARE NOT TO BE SCALED; REFER TO THE DIMENSION INDICATED. IN THE ABSENCE OF DIMENSIONS CONTRACTOR SHALL REQUEST CLARIFICATION FROM DESIGNER PRIOR TO INSTALLATION.

11. ALL WORK IS TO CONFORM TO WORKING DRAWINGS AND TECHNICAL BRIEF.

12. NO MATERIAL SUBSTITUTIONS SHALL BE MADE. DESIGNER WILL CONSIDER MATERIAL CHANGE REQUESTS ON AN INDIVIDUAL BASIS. CONTRACTOR SHALL SUBMIT SAMPLES AND CUTS FOR WRITTEN APPROVAL BY DESIGNER PRIOR TO THE START OF ANY WORK.

13. ALL MATERIALS AND EQUIPMENT SPECIFIED SHALL BE SUPPLIED, INSTALLED, CONNECTED, ERECTED, CLEANED, AND CONDITIONED AS DIRECTED BY THE SUPPLIER/MANUFACTURER, IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARD PRACTICE.

14. ALL SHOP DRAWINGS AND SUBMITTALS SHALL BE SUBMITTED TO DESIGNER FOR APPROVAL BY THE CONTRACTOR PRIOR TO WORK BEING PERFORMED, UNLESS OTHERWISE NOTED. PRIOR TO SUBMITTAL TO DESIGNER FOR APPROVAL, THE CONTRACTOR SHALL SIGN, DATE, AND STAMP, INDICATING HIS/HER REVIEW (SHOP DRAWING FORMAT WILL BE SUBMITTED ON CONSTRUCTION PHASE BY CONTRACTOR) AND APPROVAL OF THE SHOP DRAWING / SUBMITTAL.

15. THE CONTRACTOR SHALL IN ALL RESPECTS COMPLY WITH ALL REGULATIONS OF THE BUILDING MANAGEMENT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN SUCH REGULATIONS FROM THE BUILDING OWNER. IN THE EVENT OF CONFLICT BETWEEN BUILDING REGULATIONS AND OTHER CONTRACT DOCUMENTS, THE DESIGNER SHALL BE CONSULTED PRIOR TO PROCEEDING.

CONSTRUCTION NOTES

1. ALL PARTITION DIMENSIONS ARE FROM FINISHED SURFACE OR FROM FACE OF CONVECTOR ENCLOSURE, UNLESS OTHERWISE NOTED.

2. WHERE A PARTITION MEETS THE WINDOW MULLION, PROVIDE A CONTINUOUS COMPRESSIBLE FILLER STRIP. A SOUNDPROOFING FILLER PANEL SHALL BE USED INSIDE THE METAL CONVECTOR ENCLOSURE TO PREVENT SOUND TRANSMISSION BETWEEN ROOMS.

3. ALL GYPSUM BOARD PARTITIONS SHALL BE PROPERLY BRACED.

4. ALL GYPSUM BOARD SHALL BE INSTALLED VERTICALLY IN FULL LENGTH SECTIONS. IF SITE CONDITION CONFLICT WITH THE ABOVE REQUIREMENT, NOTIFY THE DESIGNER WITHOUT DELAY AND DO NOT PROCEED WITHOUT INSTRUCTIONS AND/OR SHOP DRAWING APPROVAL.

5. GYPSUM BOARD AT TOILETS AND AROUND PANTRY SINK TO BE WATER-RESISTANT TYPE.

6. PROVIDE ACCESS DOORS FOR PLUMBING, ELECTRICAL, ETC. AS REQUIRED TO ACCESS EQUIPMENT OR CONTROLS. LOCATION AND DETAIL TO BE APPROVED BY DESIGNER.

7. ALL FIRE-PROOFING ON STEEL MUST BE REPLACED IF DAMAGED OR MISSING AT CONTRACTOR'S EXPENSE.

8. ALL LOCKSETS SHALL BE MASTER KEYED AS REQUIRED BY THE BUILDING MANAGEMENT. SEE DOOR SCHEDULE / HARDWARE SCHEDULE FOR INFORMATION.

9. CONTRACTOR SHALL FURNISH AND INSTALL FIREPROOF BLOCKING IN CEILINGS OR PARTITIONS AS REQUIRED, OR WHERE WALL-MOUNTED EQUIPMENT OR CABINETRY IS INDICATED FOR A COMPLETE INSTALLATION.

10. ANY WOODWORK SHALL BE FOLLOWED LEED REQUIREMENTS.

11. CONTRACTOR TO VERIFY IN FIELD EXISTING SLAB OPENING LOCATIONS FOR BATHROOM PLUMBING. CONTRACTOR TO PROVIDE ADDITIONAL OPENINGS IF NECESSARY AND CLARIFY WITH DESIGNER AND STRUCTURE ENGINEER BEFORE COMMENCEMENT.

COORDINATION NOTES

1. SEE ENGINEER'S DRAWINGS FOR ADDITIONAL NOTES AND GENERAL INFORMATION.

2. SEE ENGINEER'S DRAWINGS FOR ALL LIGHT FIXTURE CIRCUITING, EMERGENCY AND EXIT LIGHTING, SMOKE DETECTORS, STROBE LIGHTING, ALARM SPEAKERS, SWITCHING AND RELATED WORK. LIGHT SWITCHES AND DIMMERS AS INDICATED ON INTERIOR WORKING DRAWINGS. INTERIOR PLANS ARE FOR LOCATION ONLY. CONTRACTOR IS TO VERIFY ALL LIGHT FIXTURE WATTAGE (MAX.) AND PROVIDE PROPER NUMBER OF SWITCHES AT THAT LOCATION TO SERVICE INDICATED LIGHT FIXTURES.

3. SEE ENGINEER'S DRAWINGS FOR ALL CEILING DIFFUSERS, DUCTWORK LAYOUTS, TRANSFER DUCTS, FUSIBLE LINK DAMPERS, ETC. WORKING DRAWINGS INDICATE DIFFUSERS FOR LOCATION ONLY. WHERE DISCREPANCIES OCCUR BETWEEN ENGINEERING AND INTERIOR WORKING DRAWINGS REGARDING LOCATIONS, INTERIOR WORKING DRAWINGS SHALL GOVERN IN INTERIOR AREA.

4. CONTRACTOR SHALL PROVIDE COMPOSITE DRAWINGS. I.E. FLOOR PLAN, CEILING PLAN, ELEVATION AND DETAIL, AND NECESSARY SHOP DRAWINGS COORDINATING ALL TRADES, SHOP DRAWING THE LOCATION OF SUSPENSION MEMBERS, LIGHT FIXTURES, EMERGENCY AND EXIT FIXTURES, HVAC FIXTURES, DRAPERY POCKETS, FIRE DAMPERS, ACCESS DOORS, FASCIAS, SOFFITS AND ALL OTHER ITEMS PENETRATING OR ATTACHED TO THE PLAN, CEILING AND ELEVATION.

5. ACCESS DOOR LOCATIONS TO BE REVIEWED IN THE FIELD PRIOR TO INSTALLATIONS AND THEIR LOCATIONS TO BE APPROVED BY DESIGNER.

6. SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS. MAINTAIN CEILING HEIGHT THROUGHOUT. NOTIFY DESIGNER OF ANY COMPLICATIONS WITH HEIGHT.

7. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING COMPATIBILITY OF LIGHTING FIXTURES WITH THE SPECIFIED CEILING SYSTEM.

8. CONTRACTOR TO PROVIDE INITIAL LAMPING OF ALL FIXTURES AND INSTALL APPROPRIATE LAMPS AS REQUIRED BY SPECIFIED LIGHT FIXTURE.

9. CONTRACTOR SHALL PROVIDE AND INSTALL SHALLOW DEPTH FIXTURES AS FIELD CONDITIONS NECESSITATE, WITH DESIGNER APPROVAL.


10. CONTRACTOR TO PROVIDE APPROPRIATE SIZED CUT-OUT ABOVE CEILING WHERE PARTITION WALLS EXTEND TO SLAB ABOVE, AS REQUIRED FOR CIRCULATION OF RETURN AIR TO H.V.A.C. SYSTEM. FURNISH AND INSTALL FIRE DAMPERS AS REQUIRED TO MAINTAIN THE INTEGRITY OF RATED WALLS.

11. SEE ENGINEER'S DRAWINGS FOR ALL SPRINKLER HEADS AND RELATED WORK. WORKING DRAWINGS INDICATE SPRINKLER HEADS FOR LOCATION ONLY. WHERE DISCREPANCIES OCCUR BETWEEN INTERIOR DRAWINGS AND ENGINEERING DRAWINGS REGARDING LOCATIONS, INTERIOR DRAWINGS SHALL GOVERN IN INTERIOR SCOPE OF WORK.

12. SEE ENGINEER'S DRAWING FOR ALL CIRCUITING AND RELATED WORK.

SAMPLE NOTES

1. SAMPLES OF ALL FINISHES SPECIFIED SHALL BE SUBMITTED TO DESIGNER FOR APPROVAL FOR:

APPEARANCE

COLOR

TEXTURE

MECHANICAL PROPERTIES

OTHER PROPERTIES

REQUIRED SAMPLES INCLUDE BUT ARE NOT LIMITED TO:

EACH TYPE OF FLOOR FINISH (1m X 1m)

EACH TYPE OF WALL FINISH (1m X 1m)

- ESPECIALLY, PAINT SAMPLES FOR GYPUM BOARD SURFACES TO BE PROVIDED ON 0.6m X 0.6m PIECES OF GYPUM BOARD.

EACH TYPE OF CEILING FINISH (1m X 1m)

CLADDING MATERIAL (1m X 1m)

IRONMONGERY (1 UNIT PER VENDOR)

SANITARY WARE (1 UNIT PER VENDOR)

TOILET ROOM ACCESSORIES (1 UNIT PER VENDOR)

DRAINS, OUTLETS, AND COVERS (1 UNIT PER VENDOR)

CEILING ACCESSORIES (TRIM, ACCESS PANEL, ETC)

ALL VISIBLE ITEMS (1 UNIT PER VENDOR)

CONTRACTOR SHALL SUBMIT THREE IDENTICAL SAMPLES OF EACH ITEM FOR REVIEW. ADDITIONALLY, THE CONTRACTOR SHALL SUBMIT AN EXTREME RANGE OF SAMPLES WHEN THE DEGREE OF MARKING OR COLOR CANNOT BE REPRESENTED BY A SINGLE SAMPLE. A RANGE WILL CONSTITUTE ONE SAMPLE.

2. EACH SAMPLE SHALL HAVE A LABEL INDICATING:

- NAME OF PROJECT

- NAME OF CONTRACTOR AND SUPPLIER, IF APPLICABLE

- MATERIAL OF EQUIPMENT REPRESENTED

- PLACE OF ORIGIN

- NAME OF PRODUCER AND BRAND (IF ANY)

- LOCATION IN PROJECT (INCLUDING FACILITY AND CONTRACT NUMBER)

- SPECIFICATION SECTION AND PARAGRAPH NUMBER

- DATE SUBMITTED

- ANY OTHER INFORMATION TO FULLY DESCRIBE THE ITEM.

FINISH NOTES

1. ALL WALLS SHALL BE PROPERLY PREPARED (SPACKLED, SANDED, ETC.) FOR PAINTING AND/OR WALL FABRIC AS PER FINISH PLAN AND MANUFACTURER'S SPECIFICATIONS.

2. ALL PAINTS SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS FOR THE PARTICULAR SURFACE.

3. ALL SURFACES WHICH ARE TO BE PAINTED SHALL RECEIVE (1) COAT OF PRIMER AND (2) COATS OF FINISH PAINT. (3) COATS TOTAL.

4. WHERE GRANITE OR MARBLE FLOORING IS SPECIFIED, CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING/APPLYING SEALANT AS SPECIFIED OR AS RECOMMENDED BY SUPPLIER, FOR A CLEAN, LASTING SURFACE.

5. CROSS JOINTS NECESSARY DUE TO LENGTH OF ROLLS RECEIVED, SHALL BE PLACED TO AVOID OCCURRENCE AT CONSPICUOUS LOCATIONS NEAR DOOR OR AT DOORWAYS AND ENTRIES PERPENDICULAR TO DOORS OR ENTRIES. SEAMS OCCURRING PARALLEL TO DOORS SHALL BE CENTERED DIRECTLY UNDER THE DOOR. CONTRACTOR TO SUBMIT SEAMING DIAGRAM FOR DESIGNER'S REVIEW.

6. SEAMS SHALL BE TRIMMED AND SEAMED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS.

7. ALL COMPOSITE WOOD AND AGRIFIBER PRODUCTS SHOULD NOT CONTAIN UREA-FORMALDEHYDE RESIN.

8. ALL ADHESIVES AND SEALANTS SHOULD COMPLY WITH MAXIMUM ALLOWED VOC LEVELS REQUIREMENTS.

9. ALL MATERIAL TO COMPLY LEED REQUIREMENTS INCLUDING VOC LEVEL LIMITATION.